The sites below gathered these
from manufacturers like
White Rodgers
Lux
and others to show usual terminal
designations:
From
http://highperformancehvac.com/thermostat-wiring-colors.html
:
-
" R – The
R terminal is the power for the thermostat. This comes from the
transformer usually located in the air handler for split
systems but you may find the transformer in the condensing
unit. For this reason, it is a good idea to kill the power at the condenser
and
the air
handler before changing or working on the wiring at the thermostat.
If you have a package unit then the transformer is in the package
unit.
-
RC – The RC terminal is designated for the
power for cooling. Some HVAC systems use two transformers. A transformer
for cooling and a transformer for
heating. In this case the power from the transformer in the air conditioning
system would go to the thermostat terminal. It should be noted that a jumper
can be installed between RC and RH for a heating and cooling system equipped
with a single transformer.
-
RH – The RH terminal is designated
for the power for heating. See RC above for an explanation. It should be
noted that
a jumper
can be installed between RC and RH for a heating and cooling system equipped
with a single transformer.
-
Y – This is the
terminal for cooling or air conditioning and goes to the compressor relay.
Typically a thermostat wire
pull is made to the air handler on split systems and then this wire
is spliced for the separate wire pull which is made to the condenser.
Some manufacturers
put a terminal board strip near the control board in the air handler
so a splice is not needed.
-
Y2 – This is the thermostat terminal
for cooling second stage if your system is so equipped. Many systems
only have a single compressor
but if
you have two compressors which should only operate off of one thermostat
then you need the Y2 thermostat terminal for second stage cooling.
-
W – This is the thermostat terminal for heating.
This wire should go directly to the heating source whether it be a gas or
oil furnace, electric furnace, or boiler, electric heat, auxiliary heat on a heat pump w
defrost output from outdoor unit to activate electric heat
and turn on the AUX. heat lamp
-
W2 – This is the thermostat terminal used
for second stage heat. There are gas furnaces with low fire and high fire
and some depend on control from a two-stage heating thermostat with a W2
terminal. Heat Pumps use staging for auxiliary heat and need a W2 terminal.
-
G – This is the thermostat terminal used for
the fan relay to energize the indoor blower fan. On a split system the blower
fan is in the air handler while with a package unit the blower fan is in
the outdoor package unit.
-
C – This is the thermostat terminal which
originates from the transformer and is necessary to complete the 24 volts
power circuit in the thermostat but only if the thermostat consumes electricity
for power. Many digital thermostats require 24 volts for power so the common
wire is necessary.
-
O or B – These thermostat terminals are for
heat pumps and the B thermostat terminal is used on for Rheem or Ruud and
any manufacturer that energizes the reversing valve in heating mode for the
heat pump. Most other manufacturers of heat pumps will utilize the reversing
valve for cooling and the O thermostat terminal will be utilized for this
purpose. This wire goes to outside heat pump condenser where the reversing
valve is located. Energize to heat some systems, Rheem Ruud.
-
B or X – common side of transformer. some electronic
thermostats indicator lamps. confused with B Reversing valve energize to
heat
above. York and Trane use B common.
-
E – This thermostat
terminal is for heat pumps and stands for Emergency Heating. If for whatever
reason the heat pump condenser
fails and it is necessary
to run the heat there is an option on heat pump thermostats for emergency
heating. Basically this simply utilizes the back-up heat source many
heat pumps have to heat the home without sending a signal to the condenser
to
run for heat."
More on this can be found from jsmeenan
site as he gives colors others might choose on wiring harnesses if
available:
" E] emergency heat relay on a heat pump. . X2]
on Trane, outdoor anticipator reset.
Used on GE Trane American Standard and some Carrier.
L] service indicator lamp.
Numbers, see diagrams, re stages of electric heat especially
on York Borg Warner Coleman-Evcon, Frasier Johnson Air-pro.
X2], 2nd stage Electric Heat on GE Trane American Standard. indicator
lamp or misc. contacts on other systems"
Compiled from Honeywell thermostat manuals:
"Old Label_________New Label__Description
R, V-VR or VR-R ______ R_____ 24 VAC, Return
Y,Y1 or M____________ Y_____ Stage 1 Cooling Heating
Circuit
O or R _______________ 0______Reversing Valve,
(Cooling Mode]
B ___________________ B_____ Reversing Valve
(Heating Mode]
F or G _______________ G_____ Fan control relay
Y2 __________________ Y2____ 2nd Stage Cooling Circuit
W1 or W2 or W-U _____ W2____ 2nd Stage Heating Control
L or X _______________ L _____ System Monitor LED
E or X2 ______________ E_____ Emergency Heating Circuit
C,X or B _____________ C_____ 24 VAC, Transformer
Common
How to set a thermostat anticipator.
By eMailing questions and responses, the Member
of this board is protected from SPAM and
unsavory sites by filters through my eMail program. Your posts will be answered after filtering and editing to assure general
readership acceptability.
To post, click =>if
Java enabled
If Acrobat enabled
if not, eMail